SIRIUS ESE Lightning Arrester
Design
- Non-Electronic ESE
- No use of battery or external power source
- 304L (Inox) Stainless Steel – suitable for any environmental conditions
Testing
- Tested & certified for NF C 17-102 (2011) standard UNE 21186:2011 standard
- Mechanical Test
- Environmental Test a) Salt Mist Test- 3 Cycles – 72 Hours b) Humid Sulphur Test – 7 Cycles – 168 Hours
- 200 kA (10/350 µs) Lightning Impulse Current Test
- △T = 60 μs – Early Streamer Emission Test
- CPRI (Central Power Research Institute Govt of India) – 70 kA (8/20 µs) tested
Suitable for various down conductors
| Protection radius as per NF C 17-102 (2011) | ||||
|---|---|---|---|---|
| Mast Height h (m) | Level I Very High | Level II High | Level III Medium | Level IV Standard |
| 2 | 31 | 35 | 39 | 43 |
| 3 | 47 | 52 | 58 | 63 |
| 4 | 63 | 69 | 78 | 85 |
| 5 | 79 | 86 | 97 | 107 |
| 6 | 79 | 87 | 97 | 107 |
| 8 | 79 | 88 | 98 | 108 |
| 10 | 79 | 88 | 99 | 109 |
| 15 | 80 | 89 | 101 | 111 |
| 100 | 80 | 89 | 105 | 120 |